Household/Building Technology Power Solutions - Flipbook - Page 21
DIN-RAIL MOUNT
PAGE 21
TBL
15–150 Watt
Model
¡ Low profile, module depth only 55 mm
¡ Fits into flat control panels used in
building automation
¡ Safety class ll product
¡ UL 1310 class II, NEC class 2 compliance (models up to 90 W)
¡ UL 508 listed
¡ Universal input range 85 to 264 VAC
(auto range for 150 Watt models)
¡ Operating temperature range:
–25°C to +70°C max.
¡ Adjustable output voltage
¡ Short circuit and overload protection
¡ DC–OK indicator
¡ Easy snap-on mounting on DIN-rail or
with wall mounting bracket (included)
¡ 3-year product warranty
TBL 015-105
TBL 015-112
TBL 015-124
TBL 030-112
TBL 030-124
TBL 060-112
TBL 060-124
TBL 090-112
TBL 090-124
TBL 150-112
TBL 150-124
Dimension Table
Output
Power
(max.)
Output
Voltage*
(nom.)(adjust.)
Output
Current
(max.)
12 W
15 W
15 W
30 W
30 W
54 W
60 W
72 W
90 W
120 W
150 W
5.0 VDC
12 VDC
24 VDC
12 VDC
24 VDC
12 VDC
24 VDC
12 VDC
24 VDC
12 VDC
24 VDC
2.4 A
1.25 A
0.63 A
2.5 A
1.25 A
4.5 A
2.5 A
6.0 A
3.75 A
10 A
6.25 A
73%
79%
81%
81%
83%
83%
85%
84%
86%
84%
87%
Weigth
Model
TBL 015
Width [W]
[g]
26.3 mm (1.04)
100
TBL 030
52.5 mm (2.07)
160
TBL 060
70.0 mm (2.76)
230
TBL 090
105 mm (4.13)
340
TBL 150
175 mm (6.89)
625
TPC
30–120 Watt
Model
¡ For industrial, office and residential
environments
¡ Meets European ErP directive (green
mode),